Vol. 10 (2007 year), No. 4

Veselov A.E., Nevretdinov Yu.M., Yaroshevich V.V., Kabeev I.E., Fastiy G.P., Tokareva E.A.
Development of technical measures on compensation of short circuit capacitor currents on the ground and on restriction overvoltages in industrial distributive network systems

The analysis of the current actions of Joint Stock Company KAZ load on the hydroelectric power station NIVA-3 generators with the asymmetrical regimes by means of estimation of torsional oscillations and tangential vibrations in the generators has been executed. It has been shown that the double frequency tangential force practically does not create significant vibration displacements with the natural frequency offset of the frontal parts basket. The vibration rates and shock displacements considerably increase in the near-resonant region. The conclusion has been made that the intensive action of the transient currents superposition is the result of the reducing of the water turbines replacement life and an increase in the remedial maintenance frequency.

(in Russian, стр.6, fig. 1, tables. 2, ref 7, Adobe PDF, Adobe PDF 0 Kb)

Vol. 12 (2009 year), No. 1

Nevretdinov Yu.M, Fastiy G.P., Yaroshevich V.V.
Analysis of electrical energy quality indexes registration on buses of supply substations

The paper describes results of homogeneous can sterilization modeling. The influence of nonuniformity of temperature field and tin inertia on difference of sterilization efficiency in random tins has been evaluated.

(in Russian, стр.7, fig. 8, tables. 3, ref 28, Adobe PDF, Adobe PDF 0 Kb)

Vol. 12 (2009 year), No. 1

Nevretdinov Yu.M., Karpov A.S., Fastiy G.P.
Perfection of communication lines' protection from influence of high-voltage network currents

Electrical energy quality indexes registration results analysis has been performed on buses of a supply substation 40A of Kovdor substation group. The power system and 35 kV side load do not include electrical energy quality decreasing sources; voltage distortions control in the common connection point of several consumers are insufficient for distorting sources localization.

(in Russian, стр.5, fig. 4, tables. 1, ref 2, Adobe PDF, Adobe PDF 0 Kb)

Vol. 12 (2009 year), No. 1

Veselov A.E., Fastiy G.P., Tokareva E.A.
Technical losses of active electrical energy in enterprises' exterior circuits

Experimental research results of lightning protection schemes at inoperative circuit area 110 kV have been showed in this work. The experiments have been carried out during pulses generation up to 40 kV with protective devices modeling, overhead transmission line insulation "direct" flashovers and "back" flashovers. The results have shown high efficiency of cascade substations lightning protection even under application of III group valve dischargers at transmission line approach. Experiments in operative circuit allow taking information about overvoltages development, which rationally can be used under mathematical models' validity control.

(in Russian, стр.5, fig. 1, tables. 0, ref 4, Adobe PDF, Adobe PDF 0 Kb)

Vol. 14 (2011 year), No. 3

Veselov A.E., Yaroshevich V.V., Fastiy G.P.
Improving the efficiency of industrial power supply systems using current-limiting devices

The analysis of developments in the field of increasing efficiency of functioning enterprise electric power supply circuits has been held. The attention has been paid to improving quality of voltage at deep limiting short-circuit currents with current-limiting devices and switching devices based on power semiconductor technology. The new schemes of electricity distribution networks 6, 10 and 0,4 kV with parallel operation of sections of busbars have been proposed and thoroughly analyzed. It has been shown that implementation of the developed schemes leads to substantial improvement in power quality and limit short circuit currents in industrial power networks.